(consumed power) the output current is 20mA.
Example 2: if the output signal is ±10VDC, the scaling parameters can
be set as follows:
"Min IN"= -100(kW), "Max IN"= 100(kW) therefore "Min O." must be
0.0(%) (0V) and "Max O." must be 100.0(%) (+10VCC), that is to say,
when the power is -100(kW), the output is -10V, when it is "0", the output
is 0V and when the power is 100kW the output voltage is +10VDC.
USEFUL INFORMATION
The instrument can retransmit the current/power/energy that has been
measured according to the direction of the current that flows in the
primary/secondary of the connected current transformer (where avail-
able), as illustrated in the following figures:
It is very important to respect the polarity of the measuring inputs,
otherwise the instrument will not work properly. A wrong connec-
tion of the current inputs will not allow any retransmission of
signals from the output 0 to 20mA, 0 to 10V, etc.
However, it is possible to measure and retransmit currents/powers
according to the direction of their flow using correctly the parameters
"Min O./ Max O." and Min IN/ Max IN".
For example, it is necessary to measure a power up to 100kW consid-
ering that this power can be consumed or generated by the system:
Example 1:
If the output signal is 0-20 mA, the scaling parameters can be set as
follows:
"Min IN" must have a value of 0(kW) and "Max IN" of 100(kW), therefore
"Min O." is 50.0(%) (10mA) and "Max O." is 100.0(%) (20mA).
When the power is –100kW (generated power), the output is 0mA, when
the power is "0" the output current is 10mA and when the power is 100kW