is to be entered making various attempts starting from a minimum value,
for example Fi.C=3. The datum will not remain stable, therefore Fi.C
is to be increased; in our case the optimum value is Fi.C=15.
A.ou: menu to program the parameters relating to the analogue output.
Lo.A: value to be expressed as % of the output range (0/20mA-0/10V)
to be generated in correspondence with the minimum measured value
(Lo.E/Lo parameters). Value programmable within the range: 0.00 <
Lo.A < 99.99. Example: Lo.E=Lo=-100°C that must correspond to a
retransmitted signal of 4mA.
Lo.A (%) = 100 x ?mA that in our example corresponds to:
20
100x4mA/20 = 20%, therefore enter 20.00.
Example: Lo.E=Lo=-100°C that must correspond to a retransmitted
signal of 1V.
Lo.A (%) = 100 x ?V that in our example corresponds to:
10
100x1V/10 = 10%, therefore enter 10.00.
Hi.A :
value expressed as % of the output range (0/20mA-0/10V) to be
generated in correspondence with the maximum measured value (Hi.E/Hi
parameters). Value to be programmed within the range: 0.00 < Hi.A < 99.99.
Example: Hi.E=Hi=+200°C that must correspond to a retransmitted
signal of 18mA.
Hi.A (%) = 100 x ?mA that in our example corresponds to:
20
100x18mA/20 = 90%, therefore enter 90.00.
Example: Hi.E=Hi=+200°C that must correspond to a retransmitted
signal of 5V.