CARLO GAVAZZI MDI 40 TF - CONFIGURATION SOFTWARE Instrukcja Użytkownika Strona 6

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 27
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 5
6
ENGLISH
COMPENSATION (TC)
Cold junction, within a temperature range from 0 to 50°C of ambient
temperature.
ALARM SET-POINTS
2 independent standard set-points;
Alarm type: the alarm is active only for under/over-range, high alarm, low
alarm, low alarm with disabling at power-on, high alarm with latch, low
alarm with latch.
Interaction of the two set-points (on request).
Set-point adjustments: programming of minimum and maximum value;
Set-point and hysteresis level: programmable from 0 to 100% of the
displayed range;
Activation/deactivation time delay: programmable from 0 to 255 sec-
onds;
Relay status: selectable; normally energized/de-energized;
Output contacts: 2 x SPDT; rating: 5A, 250VAC/VDC, 40W/1200VA,
130.000 cycles;
Min. response time: 400 ms (filter excluded, set-point activation time
delay: “0”);
Insulation: 2000VRMS between output and measuring input; power-
supply for signal output
FILTER
Operating range: from 0 to 3999;
Filtering coefficient: from 1 to 255
DATA HOLD
automatic storage (RAM only) of the minimum and maximum value
measured from the previous storage reset onwards.
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · [email protected]
Przeglądanie stron 5
1 2 3 4 5 6 7 8 9 10 11 ... 26 27

Komentarze do niniejszej Instrukcji

Brak uwag