CARLO GAVAZZI
CONTROLS
SERIAL COMMUNICATION PROTOCOL
WM4-96
V1 R3
Page
3.1.23 Installed power coding
Installed power
XXXXXXXX XXXXYYYY
XXXXXXXXXXXX -à MANTISSA YYYY -à EXPONENT
The mantissa is lower than 2000 and the exponent lower than 16.
The YYYY value corresponds to the value on the "INF" table, with which it is possible to find the
engineering unit to be associated to the XXXXXXXXXXXX mantissa.
3.1.24 dmd variable coding
VARIABLE Bit VARIABLE bit
V L1-N 0 W L2 13
V L2-N 1 W L3 14
V L3-N 2
W
15
VL-N
3 var L1 16
V L1 4 var L2 17
V L2 5 var L3 18
V L3 6
VAR
19
V
7 VA L1 20
A L1 8 VA L2 21
A L2 9 VA L3 22
A L3 10
VA
23
A
11
PF
24
W L1 12
4 BYTE
XXXXXXXX XXXXXXXX n
th
bit=0 variable not selected; n
th
bit=1 variable selected
XXXXXXXX XXXXXXXX n
th
bit=0 variable not selected; n
th
bit=1 variable selected
The maximum number of selectable variable is 8.
3.1.25 SMS event coding
VARIABLE bit
Alarm1 0
Alarm2 1
Alarm3 2
Alarm4 3
4 BYTE
XXXXXXXX XXXXXXXX n
th
bit=0 variable not selected; n
th
bit=1 variable selected
XXXXXXXX XXXXYYYY n
th
bit=0 variable not selected; n
th
bit=1 variable selected
Only the first 4 bits (YYYY) are considered.