SERIAL COMMUNICATION PROTOCOL
WM4-96
V1 R3
Page
6.2 RS232 INTERFACE
General technical specifications Note
Baud rate 2400, 4800, 9600, 38400 bps
Data format 1start/8 data / 1 stop bit / no parity
Address Not managed A
Note:
A. Nevertheless in the address cell a value from 1 to 255 must be.
9-pole female RS232 connector Note
Pin 1 DCD
Used only for modem connection
Pin 2 TX
To be connected to the RX terminal
of the PC COM
Pin 3 RX
To be connected to the TX terminal
of the PC COM
Pin 4 Not used
Pin 5 GND
To be connected to the GND terminal
of the PC COM
Pin 6 Not used
Pin 7 Not used
Pin 8 Not used
Pin 9 RING
Used only for modem connection
Note: to connect WM4 with a PC use a serial cable with “pin to pin” connections.
Timing characteristics for RS232 communication msec
T response: max answering time 600ms
T response: typical answering time 100ms
T delay: minimum time for a new query 10ms
T null: maximum interruption time on the request frame 50msec
Note: T null is independent of the selected baud-rate value
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · [email protected]