CARLO GAVAZZI
CONTROLS
SERIAL COMMUNICATION PROTOCOL
WM24-96
V1 R0
Page
11
NOTE: a digital output can be used as remote control output only if the relevant “digital output type”
variable stored in EEPROM is correctly set (see paragraph 3.2.9).
2.2.5 Energy and utility metering and digital inputs
The number and the type of the working energy meters are depending on the “counter” parameter,
according to the following table.
counter
TOT TOT – PAR TOT – 1.CN TOT – 2.CN
RAM address
kWh + kWh tot kWh + kWh + 0241h
kWh - kvarh tot kWh - kWh - 0245h
kvarh C+ kWh t1 kvarh C+ kvarh C+ 0249h
kvarh C- kvarh t1 kvarh C- kvarh C- 024Dh
kvarh L+ kWh t2 kvarh L+ kvarh L+ 00E8h
kvarh L- kvarh t2 kvarh L- kvarh L- 00ECh
kWh t3 m
3
GAS day m
3
GAS tot 00F0h
kvarh t3 m
3
GAS night m
3
WATER tot 00F4h
kWh t4 00F8h
kvarh t4 00FCh
Digital inputs determinate the active tariff for energy metering (t1, t2, t3 or t4) or for the gas tariff (day
or night), or collect gas and water pulses or the synchronisation pulses for Wdmd and VAdmd
calculation, according to the selected value of ‘counter’ parameter.
counter input description dmd synchr.
IN3 Yes
TOT
IN2
Not used
Yes
IN3 Yes
TOT – PAR
IN2
Selection of the current tariff for energy
metering Yes
IN3 Selection of the current tariff for gas
metering
No
TOT – 1.CN
IN2
Gas pulses acquisition (weight of the pulse
=‘PrESCAL Cn.1’)
No
IN3 Water pulses acquisition (weight of the
pulse =‘PrESCAL Cn.2’)
No
TOT – 2.CN
IN2
Gas pulses acquisition (weight of the pulse
=‘PrESCAL Cn.1’)
No
If “counter” parameter is set to TOT – PAR”, the coding of the energy tariffs is the following.
Tariff IN2 IN3
t1 open open
t2 open close
t3 close open
t4 close close
The current tariff is highlighted from the blinking of the t1, t2, t3 or t4 indication in the relevant display
page.
If “counter” parameter is set to TOT – 1.CN”, the coding of the gas tariffs is the following.
Tariff IN3
Day open
Night close
t3 open
t4 close