3.2.14 dig_on1(2)/dig_off1(2)
MINIMUM MAXIMUM FORMAT
–variable f.s.(W∑, var∑, Wdmd only)
0 (all the remaining variables)
Variable f.s. As per range_dig1(2)
The f.s. for each variable is depending on the instrument model, on the range parameter and on the
CT and VT ratios.
If CT ≤ 10, VT ≤ 10.0 and CT*VT ≤ 10.0, the following table is to be considered:
RANGE 0 1 2 3VARIABLE
MODEL F.S.
100 VLL / 5A 1999 (199.9) 1999 (1999)
-
208 VLL / 5A 1999 (199.9) 1999 (1999)
260 (26.0k)
400 VLL / 5A 1999 (199.9) 1999 (1999) 1999 (19.99k) 499 (49.9k)
W ∑, VA ∑,
var ∑,
W dmd,
VA dmd
660 VLL / 5A 1999 (1999) 1999 (19.99k) 824 (82.4k) -
100 VLL / 5A 1999 (199.9) 1200 (1200) - -
208 VLL / 5A 1999 (199.9) 1999 (1999) 250 (2.50k)- -
400 VLL / 5A 1999 (199.9) 1999 (1999) 480 (4.80k) -
V ∑
660 VLL / 5A 1999 (1999) 792 (7.92k) - -
100 VLL / 5A 100 (1.00) - - -
208 VLL / 5A 100 (1.00) - - -
400 VLL / 5A 100 (1.00) - - -
PF ∑
660 VLL / 5A 100 (1.00) - - -
100 VLL / 5A 100 (100) - - -
208 VLL / 5A 100 (100) - - -
400 VLL / 5A 100 (100) - - -
ASY V
660 VLL / 5A 100 (100) - - -
If VT is between 10.1 and 100.0, the values between brackets multiplied by 10 are valid when
considering V ∑.
If VT is between 100.1 and 1000.0, the values between brackets multiplied by 100 are valid when
considering V ∑, and so on.
If CT x VT is between 10.1 e 100.0, the values between brackets multiplied by 10 are valid when
considering the powers.
If CT x VT is between 100.1 e 1000.0, the values between brackets multiplied by 100 are valid when
considering the powers, and so on.
3.2.15 rel_type1 and rel_type2
MINIMUM MAXIMUM FORMAT
0 1 1111
VALUE CODE DESCRIPTION
0 Normally De-energised
1 Normally Energised
3.2.16 rel_delay1 and rel_delay2
MINIMUM MAXIMUM FORMAT
0 255 1111 [seconds]