2.2.6 Energy and utility meters reading
The meter values are to be read from the RAM as explained in the following examples.
Example 7: Reading of total energy meter: kWh (tot) and kvarh (tot) (TOT-PAR mode)
Value request frame (8 byte):
01h 04h 02h 41h 00h 03h CRC CRC
Value answer frame (13 byte):
01h 04h 08h FFh D6h 02h 00h 57h AAh 04h 00h CRC CRC
Stored value (kWh tot): 0002D6FFh 18611.1 kWh
Stored value (kvarh tot): 0004AA57h 30575.1 kvarh
Example 8: Reading of the utility meters: gas (tot) and water (tot) (TOT-2.CN)
Value request frame (8 byte):
01h 04h 00h F0h 00h 04h CRC CRC
Value answer frame (13 byte):
01h 04h 08h FBh 5Ah 1Ah 00h 4Ah 1Ch 19h 01h CRC CRC
Stored value (m
3
gas tot): 001A5AFBh 172722.7 m
3
Stored value (m
3
water tot): 01191C4Ah 1842285.8 m
3
2.2.7 Resetting energy and utility meters
Energy and utility meters are to be reset using the following fixed frames.
Example 9: total meters reset command
1-word write request command (8 byte):
01h 06h 01h 00h A5h F0h CRC CRC
Write answer command (8 byte):
01h 06h 01h 00h A5h F0h CRC CRC
The reset value is 0. The meters which are reset by this command are depending on the “counter”
parameter:
- counter=TOT-PAR Reset meters: kWh (tot), kvarh (tot)
- counter=TOT, TOT-1.CN or TOT-2.CN Reset meters: kWh (+),kWh (-)
kvarh C+, kvarh C-, kvarh L+, kvarh L-