corresponding values (Lo.E = Lo, Hi.E = Hi), if the same value is to be
both measured and displayed.
different values, if the signal to be measured is different from the one
to be displayed (see examples of Lo and Hi).
inverted values, if an increasing signal to be measured must corre-
spond to a decreasing value to be displayed (scale inversion).
Example:
Lo.E=4.00 mA Lo=1800 mbar; Hi.E=19.99 mA Hi=0 mbar,
means that when the measured value increases from 4 to 20mA, the
displayed value decreases from 1800 mbar to 0.
As you can see, the scales can be programmed with absolute freedom.
NOTE: to display temperature values as °F, it is necessary to program
the electrical scale as °C and enter the values for the displayed scale
according to the following relationship:
°F = (1.8 x °C) + 32.
Example:
Lo.E=-50 °C Lo=-58 °F; Hi.E=+760 °C Hi=+1400 °F,
means that the new measuring range becomes -58 °F to +1400 °F. The
data to be entered in the displayed scale can be calculated either by
means of the above mentioned °F relationship, or using the data of the
relevant measuring range (see chapter Technical Features, paragraph
Inputs (temperature).
diS : menu to select the displaying mode.
35 : displaying at 3
1
/
2
digit (1999)
30 : displaying at 3 digit + dummy zero (9990).
SP.1 : menu to select the programming of the set-point parameters.
tYP : selection of the type of control.
oFF : signalling of the abnormal condition. The relay is activated when
a burn-out condition occurs or the measurement is out of the electrical
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · [email protected]