set alarm value, but also with regards to the alarm type: the hysteresis
value is summed to the set value if the
alarm type is do and subtracted
from the set value if the alarm type is uP.
Example:
do alarm, SEt=220 (value of the ON alarm status), hysteresis
HYS=12resulting OFF value (end of alarm status): 232 (resulting
from 220 +12).
uP alarm, SEt=220 (value of the ON alarm status), hysteresis
HYS=12 resulting OFF value (end of alarm status): 208 (resulting
from 220 - 12).
NOTE: the hysteresis is to be programmed according to the displayed
range.
oF.d : programming of the value, expressed in seconds, of the time
delay at the alarm set-points deactivation (OFF).
Value to be programmed within the range:0 oF.d 255.
This delay can be useful when it is necessary to guarantee the alarm
output activation for a sufficiently long time which is to be acquired by the
processing system connected downstream LDI35.
on.d : programming of the value, expressed in seconds, of the time
delay at the alarm set-points activation (ON). This value is to be
programmed within the range: 0 on.d 255. This value can be useful
when it is necessary to avoid the alarm set-points activation if the alarm
duration is not long enough. Example: when the pressure of a liquid to
be measured decreases very quickly because of air bubbles, but this is
not a danger for the monitored plant.
rLY : selection of the normal status of the relay coil.
nd : normally de-energized coil.