ENGLISH
alarm with latch.
Set-point and hysteresis level: programmable from 0 to 100% of the
displayed range;
Activation/deactivation time delay: programmable from 0 to 255 seconds;
Relay status: selectable; normally energized/de-energized;
Output contacts: 1 SPDT; rating: 5A, 250VAC/VDC, 40W/1200VA,
130.000 cycles;
min. response time: 500 ms (filter excluded, set-point activation time
delay: “0”);
Insulation: 2000VRMS between output and measuring inputs; 2000VRMS
between output and excitation output.
DIGITAL FILTER
Operating range: from 0 to 1999 / 9990;
Filtering coefficient: from 1 to 255.
DATA HOLD
Automatic storage (RAM only) of the maximum value measured from the
previous storage reset onwards.
EXCITATION OUTPUT VOLTAGE (on request)
15 VDC insulated, not stabilized / max. 40 mA.
EXCITATION OUTPUT INSULATION
100VRMS between output and measuring input
4000VRMS between output and AC power supply input
500VRMS between output and DC power supply input.